S1DXM Timers Specifications
Specifications for this product appear below.
| Item | Specifications | |||||||
|---|---|---|---|---|---|---|---|---|
| Rating | Rated operating voltage | 24VAC | 100 to 120VAC | 200 to 220VAC | 220 to 240VAC | 12VDC | 24VDC | |
| Rated frequency | 50/60Hz common | - | ||||||
| Rated power consumption | Max. 3 VA (at 24 VAC) |
Max. 3 VA (at 100 VAC) |
Max. 3 VA (at 200 VAC) |
Max. 3 VA (at 220 VAC) |
Max. 2 W (at 12 VDC) |
Max. 2 W (at 24 VDC) |
||
| During time delay | Approx. 3mA | Approx. 3mA | Approx. 3mA | Approx. 3mA | Approx. 5mA | Approx. 3mA | ||
| After time delay | Approx. 80mA | Approx. 20mA | Approx. 13mA | Approx. 13mA | Approx. 70mA | Approx. 40mA | ||
| Rated control capacity | Timed -out 2 Form C: 7A 250V AC (resistive load) | |||||||
| Timed -out 4 Form C: 5A 250V AC (resistive load) | ||||||||
| Operation mode | S1DXM-A Power on delay operation fixed (Power display: ON/green; Operation display (when output is on): UP/orange) |
|||||||
| S1DXM-M 4 switchable operations: Power ON-delay/Power Flicker OFF start/Power Flicker ON start/Power One-shot (Power display: ON/green; Operation display (when output is on): UP/orange) |
||||||||
| Time accuracy*1 | Operating time fluctuation & Power off time change error | Max. ±1 %, (power off time change at the range of 0.1 s to 1 h), 1 s range: Max. ±1 % and 10 ms*2 | ||||||
| Voltage error | Max. ±1 % (at the operating voltage changes between -20 to +10%), 1 s range: Max. ±1 % and 10 ms*2 | |||||||
| Temperature error | Max. ±5% (at 20°C ambient temp. at the range of -10 to +50°C/ +14 to +122°F) | |||||||
| Setting error | Max. ±10%, 1 s range: Max. ±10% and 20 ms | |||||||
| Contact | Contact arrangement | Timed-out 2 Form C, Timed-out 4 Form C | ||||||
| Contact resistance (Initial value) | Max. 100mohm (at 1A, 6V DC) | |||||||
| Contact material | Timed-out 2 Form C type: Silver alloy, Au plating | |||||||
| Timed-out 4 Form C type: Silver alloy, Au plating | ||||||||
| Life | Mechanical (constant) | Min. 107 | ||||||
| Electrical (constant) | 2 × 105(at rated control capacity) | |||||||
| Mechanical | Vibration resistance | Functional | 10 to 55Hz: 1 cycle/min double amplitude of 0.25mm (10min on 3 axes) | |||||
| Destructive | 10 to 55Hz: 1 cycle/min double amplitude of 0.375mm (1h on 3 axes) | |||||||
| Shock resistance | Functional | Min. 98m/s2 (4 times on 3 axes) | ||||||
| Destructive | Min. 980m/s2 (5 times on 3 axes) | |||||||
| Electrical | Allowable operating voltage range | 80 to 110% of rated operating voltage | ||||||
| Reset time | Max. 0.1s | |||||||
| Insulation resistance (Initial value) | Between live and dead metal parts, between input and output, between contact sets, between contacts Min. 100 Mohm (at 500 V DC megger) | |||||||
| Breakdown voltage (Initial value) | Between live and dead metal parts: 2,000 Vrms for 1 min Between input and output: 2,000 Vrms for 1 min Between contact sets: 2,000 Vrms for 1 min Between contacts: 1,000 Vrms for 1 min |
|||||||
| Max. temperature rise | 70°C/ 158°F | |||||||
| Operating conditions | Ambient temperature | -10 to 50°C/ +14 to 122°F | ||||||
| Ambient humidity | 35 to 85% RH (non-condensing) | |||||||
| Air pressure | 860 to 1060 hPa | |||||||
| Ripple rate | DC type only, transmission wave rectification (ripple rate: approx. 48%)*3 | |||||||
| Mass (Weight) | Approx. 45 g | |||||||
| Protective construction | IEC standard: IP40 (IP50 when using ADX18008 protective cover) | |||||||
Notes:
1) Unspecified measuring conditions are rated operating voltage (in case of DC type, ripple rate of 5% or less), ambient temp. 20°C/ 68°F, and power off time 1 second.
2) Power one-shot 1 s range: +2% and 10 ms
3) When using with a transmission wave rectification, vibration resistance and shock resistance properties worsen compared to when using a stabilized power supply.