PM5S Timers Specifications
Specifications for this product appear below.
| Item / Type | PM5S-A | PM5S-S | PM5S-M | ||
|---|---|---|---|---|---|
| Rating | Rated operating voltage | 24 to 240V AC/DC | |||
| Rated frequency | 50/60Hz common | ||||
| Rated power consumption | 2.6 VA (AC), 1.4 W (DC) | ||||
| Rated control capacity | 5A 250V AC (resistive load) | ||||
| Operating mode | Pulse ON-delay Pulse Flicker Pulse ON-Flicker Signal OFF-delay Pulse One-shot Pulse One-cycle |
Power ON-delay | Pulse ON-delay Pulse Flicker Pulse ON-flicker Signal OFF-delay Pulse One-shot Pulse One-cycle (with instantaneous contact) |
||
| Time range | 1s to 500h (Max.) 16 time ranges switchable | ||||
| Time accuracy Note:) | Operating time fluctuation | ±0.3% (power off time change at the range of 0.1s to 1h) | |||
| Setting error | ±10% (Full-scale value) | ||||
| Voltage error | ±0.5% (at the operating voltage changes between 85 to 110%) | ||||
| Temperature error | ±2% (at 20°C ambient temp. at the range of –10 to +55°C +14 to +131°F) | ||||
| Contact | Contact arrangement | Timed-out 2 Form C | Timed-out 1 Form C Instantaneous 1 Form C | ||
| Contact resistance (Initial value) | Max. 100mΩ (at 1A 6V DC) | ||||
| Contact material | Silver alloy | Au flash on Silver alloy | |||
| Life | Mechanical (contact) | 2×107 | 1×107 | ||
| Electrical (contact) | 105 (at rated control capacity) | ||||
| Electrical function | Allowable operating voltage range | 85 to 110% of rated operating voltage (at 20°C coil temp.) | |||
| Insulation resistance (Initial value) |
Min. 100MΩ (At 500V DC) |
||||
| Breakdown voltage (Initial value) | 2,000Vrms for 1 min Between live and dead metal parts 2,000Vrms for 1 min Between input and output 2,000Vrms for 1 min Between contacts of different poles 1,000Vrms for 1 min Between contacts of same pole |
||||
| Min. power off time | 100ms | ||||
| Max. temperature rise | 55°C 131°F | 65°C 149°F | |||
| Mechanical function | Shock resistance | Functional | Min. 98m/s2 (4 times on 3 axes) | ||
| Destructive | Min. 980m/s2 (5 times on 3 axes) | ||||
| Vibration resistance | Functional | 10 to 55Hz: 1 cycle/min Single amplitude of 0.35mm (10min on 3 axes) | |||
| Destructive | 10 to 55Hz: 1 cycle/min Single amplitude of 0.75mm (1h on 3 axes) | ||||
| Operating condition | Ambient temperature | –10 to +55°C +14 to +131°F | |||
| Ambient humidity | Max. 85%RH (non-condensing) | ||||
| Atmospheric pressure | 860 to 1,060hPa | ||||
| Ripple factor (DC) | 20% | ||||
| Others | Protective construction | IP40 | |||
| Weight | 120g 4.233 oz | ||||
Notes:
1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20°C 68°F ambient temperature, and 1s power off time.
2) For the 1s range, the tolerance for each specification becomes ±10ms.