PM4H/4S Timers Specifications

Timers PM4H/4S

Specifications for this product appear below.

PM4H - A/S/M Multi-Range Timers

Type Item PM4H-A PM4H-S PM4H-M
Rating Rated operating voltage 100 to 240V AC, 48 to 125V DC, 12V DC, 24V AC/DC
Rated frequency 50/60Hz common (AC operating type)
Rated power consumption Approx. 10VA (100 to 240V AC)
Approx. 2.5VA (24V AC)
Approx. 2W (12V DC, 24V DC, 48 to 125V DC)
Output rating 5A 250V AC (resistive load)
Operating mode Pulse ON-delay
Pulse Flicker
Pulse ON-flicker
Differential ON/OFF-delay (1) (2)
Signal OFF-delay
Pulse One-shot
Pulse One-cycle
Power ON-delay Power ON-delay
Power Flicker
Power ON-flicker
Power One-shot
Power One-cycle
(with instantaneous contact)
Time range 1s to 500h (Max.) 16 time ranges switchable
Time accuracy Note:) Operating time fluctuation ±0.3% (power off time change at the range of 0.1s to 1h)
Setting error ±5% (Full-scale value)
Voltage error ±0.5% (at the operating voltage changes between 85 to 110%)
Temperature error ±2% (at 20°C ambient temp. at the range of -10 to +50°C/ +14 to +122°F)
Contact Contact arrangement Timed-out 2 Form C Timed-out 1 Form C Instantaneous 1 Form C
Contact resistance (Initial value) Max. 100mΩ (at 1A 6V DC)
Contact material Silver alloy Au flash on Silver alloy
Life Mechanical (contact) 2×107
Electrical (contact) 105(at rated control capacity)
Electrical function Allowable operating voltage range 85 to 110% of rated operating voltage (at 20°C coil temp.)
Insulation resistance (Initial value) Min. 100MΩ
Between live and dead metal parts
Between input and output
Between contacts of different poles
Between contacts of same pole (At 500V DC)
Breakdown voltage (Initial value) 2, 000Vrms for 1 min Between live and dead metal parts
2, 000Vrms for 1 min Between input and output
2, 000Vrms for 1 min Between contacts of different poles
1, 000Vrms for 1 min Between contacts of same pole
Min. power off time 100ms
Max. temperature rise 55°C/ 131°F 65°C/ 149° F
Mechanical function Shock resistance Functional Min. 98m/s2(4 times on 3 axes)
Destructive Min. 980m/s2(5 times on 3 axes)
Vibration resistance Functional 10 to 55Hz: 1 cycle/min double amplitude of 0.5mm (10min on 3 axes)
Destructive 10 to 55Hz: 1 cycle/min double amplitude of 0.75mm (1h on 3 axes)
Operating condition Ambient temperature -10 to +50°C/ +14 to +122 °F
Ambient humidity 30 to 85%RH (at 20°C/ 68°F, non-condensing)
Atmospheric pressure 860 to 1, 060hPa
Ripple factor (DC type) 20%
Others Protective construction IP65 on front panel (using rubber gasket ATC18002) (only for IP65 type)
Weight 100g/ 3.527oz (Pin type)
110g/ 3.880oz (Screw terminal type)

Notes:
1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20°C/ 68°F ambient temperature, and 1s power off time.
2) For the 1s range, the tolerance for each specification becomes ±10ms.

^ Back to top

PM4H - SD/SDM - Star/Delta Timers

Type Item PM4H-SD/SDM
Rating Rated operating voltage 100 to 240V AC, 24V AC
Rated frequency 50/60Hz common
Rated power consumption Approx. 6VA (100 to 240V AC) Approx. 1.4VA (24V AC)
Rated control capacity 5A 250V AC (resistive load)
Operation mode -star-delta switching (Power ON-delay)
operation control time range 2s to 100s, 4 time ranges switchable
- switching time 0.04, 0.1, 0.3, 0.5, 0.7s (5 time range selectable)
Time accuracy
Note:)
Operation time fluctuation ±0.3% (power off time change at the range of 0.1s to 1h)
Setting error ±5% (Max. setting time value)
Voltage error ±0.5% (at the operating voltage changes between 85 to 110%)
Temperature error ±2% (at 20°C ambient temp. at the range of -10 to +50°C +14 to +122°F)
Contact Contact arrangement Star () side: Timed-out 1 Form A Delta () side: Timed-out 1 Form A
Instantaneous: 1 Form A (Instantaneous for PM4H-SDM type only)
Contact resistance (Initial value) Max. 100mohm (at 1A 6V DC)
Contact material Au flash on Silver alloy
Life Mechanical (contact) 2×107
Electrical (contact) 105 (at rated control capacity)
Electrical function Allowable operating voltage range 85 to 110% of rated operating voltage (at 20°C coil temp.)
Insulation resistance (Initial value) Min. 100Mohm Between live and dead metal parts
Between input and output
Between contacts of different poles *3
Between contacts of same pole
(At 500V DC)
Breakdown voltage (Initial value) 2, 000Vrms for 1 min Between live and dead metal parts
2, 000Vrms for 1 min Between input and output
2, 000Vrms for 1 min Between contacts of different poles *3
1, 000Vrms for 1 min Between contacts of same pole
Min. power off time 500ms
Max. temperature rise 65°C/ 131°F
Mechanical function Vibration resistance Functional 10 to 55Hz: 1 cycle/min double amplitude of 0.25mm (10min on 3 axes)
Destructive 10 to 55Hz: 1 cycle/min double amplitude of 0.375mm (1h on 3 axes)
Shock resistance Functional Min. 294m/s2 (4 times on 3 axes)
Destructive Min. 980m/s2 (5 times on 3 axes)
Operating condition Ambient temperature -10 to +50°C/ +14 to +122°F
Ambient humidity Max. 85%RH (non-condensing)
Atmospheric pressure 860 to 1, 060hPa
Others Protective construction IP65 on front panel (using rubber gasket ATC 18002)
Weight 100g/ 3.527 oz (Pin type), 110g/ 3.880 oz (Screw terminal type)

Notes:
1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage, 20°C/ 68°F ambient temperature, and 1s power off time.
2) For the 2s range, the tolerance for each specification becomes ±10ms.
3) Between contacts of different poles for SDM type only.

^ Back to top

PM4H - F Off-delay Timers

Type
Item
PM4H-F8 PM4H-F8R PM4H-F11R
Rating Rated operating voltage 100 to 120V AC, 200 to 240V AC, 24V AC, 12V DC, 24V DC
Rated frequency 50/60Hz common (AC operating type)
Rated power consumption Approx. 1.6VA (100 to 120V AC, 200 to 240V AC), Approx. 2.3VA (24V AC)
Approx. 1.1W (12V DC, 24V DC)
Rated control capacity 3A 250V AC (resistive load)
Operation mode Power OFF-delay Power OFF-delay (with reset)
Time range 1s to 10s: 3 range switchable 1min to 10 min: 3 range selectable
Time accuracy *1 Operation time fluctuation ±0.3%
Setting error ±5% (Max. setting time value)
Voltage error ±0.5% (at the operating voltage changes between 85 to 110%)
Temperature error ±2% (at 20°C ambient temp. at the range of -10 to +50°C +14 to +122°F)
Contact Contact arrangement Timed-out 2 Form C Timed-out 1 Form C Timed-out 2 Form C
Contact resistance (Initial value) Max. 100mohm (at 1A 6V DC)
Contact material Au flash on Silver alloy
Life Mechanical (contact) 107
Electrical (contact) 105 (at rated control capacity)
Electrical function Allowable operating voltage range 85 to 110% of rated operating voltage (at 20°C coil temp.), 90 to 110% (DC Type)
Insulation resistance (Initial value) Min. 100Mohm Between live and dead metal parts
Between input and output
Between contacts of different poles *3
Between contacts of same pole (At 500V DC)
Breakdown voltage (Initial value) 1, 500Vrms for 1 min Between live and dead metal parts
1, 500Vrms for 1 min Between input and output
1, 000Vrms for 1 min Between contacts of different poles *3
750Vrms for 1 min Between contacts of same pole
Min. power supply width s range type: 100ms
min range type: 2s
Min. reset time - 50ms
Max. temperature rise 55°C/ 131°F
Mechanical function Vibration resistance Functional 10 to 55Hz: 1 cycle/min double amplitude of 0.5mm (10min on 3 axes)
Destructive 10 to 55Hz: 1 cycle/min double amplitude of 0.75mm (1h on 3 axes)
Shock resistance Functional Min. 98m/s2 (4 times on 3 axes)
Destructive Min. 980m/s2 (5 times on 3 axes)
Operating condition Ambient temperature -10 to +50°C/ +14 to +122°F
Ambient humidity 30 to 85%RH (non-condensing)
Atmospheric pressure 860 to 1, 060hPa
Ripple factor (DC type) 20%
Others Protective construction IP65 on front panel (using rubber gasket ATC 18002)
(only for IP65 type)
Weight 100g/ 3.527 oz (Pin type), 110g/ 3.880 oz (Screw terminal type)

Notes:
1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20°C/ 68°F ambient temperature.
2) For the 1s range, the tolerance for each specification becomes ±10ms. When the power goes on, in rush current (0.3A) flows. Cautions should be taken. The minimum power supplying time after forced reset input is 2s or more.
3) Between contacts of different pools for F8, F11R types only.

^ Back to top

PM4H - W Twin Timers

Type Item PM4H-W
Rating Rated operating voltage 100 to 240V AC, 12V DC, 24V AC/DC, 48 to 125V
Rated frequency 50/60Hz common (AC operating type)
Rated power consumption Approx. 10VA (100 to 240V AC) Approx. 2.5VA (24V AC) Approx. 2W (12V DC, 24V DC, 48 to 125V DC)
Output rating 5A 250V AC (resistive load)
Operation mode Cyclic (OFF-start/Twin operation)
Time range 1s to 500h 16 time ranges switchable (T1, T2time setting individually)
Time accuracy Note:) Operation time fluctuation ±0.3% (power off time change at the range of 0.1s to 1h)
Setting error ±5% (Max. setting time value)
Voltage error ±0.5% (at the operating voltage changes between 85 to 110%)
Temperature error ±2% (at 20°C ambient temp. at the range of -10 to +50°C/ +14 to +122 °F)
Contact Contact arrangement Timed-out 2 Form C
Contact resistance (Initial value) Max. 100mohm (at 1A 6V DC)
Contact material Silver alloy
Life Mechanical 2×107
Electrical 105(at rated control capacity)
Electrical function Allowable operating voltage range 85 to 110% of rated operating voltage (at 20°C coil temp.)
Insulation resistance (Initial value) Min. 100Mohm Between live and dead metal parts Between input and output Between contacts of different poles Between contacts of same pole (At 500V DC)
Breakdown voltage (Initial value) 2, 000Vrms for 1 min Between live and metal parts 2, 000Vrms for 1 min Between input and output 2, 000Vrms for 1 min Between contacts of different poles 1, 000Vrms for 1 min Between contacts of same pole
Min. power off time 300ms
Max. temperature rise 55°C/ 131 °F
Mechanical function Shock resistance Functional Min. 98m/s2(4 times on 3 axes)
Destructive Min. 980m/s2(5 times on 3 axes)
Vibration resistance Functional 10 to 55Hz: 1 cycle/min double amplitude of 0.5mm (10min on 3 axes)
Destructive 10 to 55Hz: 1 cycle/min double amplitude of 0.75mm (1h on 3 axes)
Operating condition Ambient temperature -10 to +50°C/ +14 to +122 °F
Ambient humidity Max. 85%RH
Atmospheric pressure 860 to 1, 060hPa
Ripple factor (DC type) 20%
Others Protective construction IP65 on front panel (using rubber gasket ATC 18002) (only for IP65 type)
Weight 120g/ 4.233 oz (Pin type), 130g/ 4.586 oz(Screw terminal type)

Notes:
1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20°C/ 68°F ambient temperature, and 1s power off time.
2) For the 1s range, the tolerance for each specification becomes ±10ms.

^ Back to top

PM4S - Multi-range Timers

Type PM4S Multi-range Timer
Item
Rating Rated operating voltage 100 to 120V AC 200 to 240V AC 12V DC 24V DC
Rated frequency 50/60 Hz -
Rated power consumption Approx. 3.0VA/3.6VA
(at 100V AC)
Approx. 4.5VA/5.25VA
(at 120V AC)
Approx. 5.6VA/6.8VA
(at 200V AC)
Approx. 7.5VA/9.8VA
(at 240V AC)
Approx1.3W Approx1.7W
Output rating 5A 250V AC (resistive load)
Operating mode Power ON-delay
Time range A type 1s/10s/1min/10min (4 time ranges selectable)
B type 3s/30s/3min/30min (4 time ranges selectable)
C type 6s/60s/6min/60min (4 time ranges selectable)
D type 1min/10min/1h/10h (4 time ranges selectable)
E type 3min/30min/3h/30h (4 time ranges selectable)
Time accuracy Note) Operating time fluctuation ±1% (power off time change at the range of 0.1s to 1h)
Setting error ±5% (Full-scale value)
Voltage error ±1% (at the operating voltage changes between 85 to 110%)
Temperature error ±2% (at 20°C ambient temp. at the range of 10 to +50°C/ +14 to +122°F)
Contact Contact arrangement T.D.: Timed-out 2 Form C
INST.: Timed-out 1 Form C, instantaneous 1 Form C (Selected by front switch)
Contact resistance
(Initial value)
Max. 100m ohm; (at 1A 6V DC)
Contact material Silver alloy
Life Mechanical (contact) Min. 107
Electrical (contact) Min. 105(at raed control capacity)
Electrical function Allowable operating voltage range 85 to 110% of rated operating voltage
Insulation resistance
(Initial value)
Min. 100Mohm
Between live and dead metal parts
Between input and output
Between contacts of different poles
Between contacts of same pole
(At 500V DC)
Breakdown voltage
(Initial value)
2,000Vrms for 1 min Between live and dead metal parts
2,000Vrms for 1 min Between input and output
2,000Vrms for 1 min Between contacts of different poles
1,000Vrms for 1 min Between contacts of same pole
Min. power off time 100 ms
Max. temperature rise 55°C/ 131°F
Mechanical function Vibration resistance Functional 10 to 55Hz: 1 cycle/min double amplitude of 0.25mm (10min on 3 axes)
Destructive 10 to 55Hz: 1 cycle/min double amplitude of 0.375mm (1h on 3 axes)
Shock resistance Functional Min. 98m/s2 (4 times on 3 axes)
Destructive Min. 980m/s2(5 times on 3 axes)
Operating condition Ambient temperature -10 to 50°C/ +14 to +122°F
Ambient humidity 30 to 85%RH (non-condensing)
Atmospheric pressure 860 to 1,060hPa
Ripple factor
(DC type)
20%
Others Weight approx. 110g/ 3.880 oz

Notes:
1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple factor for DC), 20°C/ 68°F ambient temperature, and 1s power off time.
2) For the 1s range, the tolerance for each specification becomes ±10ms.

^ Back to top

Panasonic Electric Works Corporation of America Contact Print