KT Temperature Controllers Part Numbers
Part numbers for KT appear below. Please use the tables below to build/calculate an appropriate model number.
KT2 Series Controllers
| Base model | Power supply | Sensor input | Control output | Alarm output | Heating/ cooling control | Heater burnout alarm | Comm. function | Description | |
|---|---|---|---|---|---|---|---|---|---|
| AKT2 | 48×24×98.5mm | ||||||||
| 1 | 100 to 240V AC | Must be specified |
|||||||
| 2 | 24V AC/DC | ||||||||
| 1 | Multi-input (Thermocouple, RTD, DC current and DC voltage) | ||||||||
| 1 | Relay contact output 1a 3A 250V AC | Must be specified |
|||||||
| 2 | Non-contact voltage output (for SSR drive) | ||||||||
| 3 | Current output | ||||||||
| 2 | 0 | 0 | Blank | When both heating/cooling and communication functions are not added: Relay contact output (alarm 1): Can be used Open collector output (alarm 2): Can be used |
|||||
| 1 | 1 | 0 | Blank | When only heating/cooling function is added: Relay contact output (alarm 1): Cannot be used Open collector output (alarm 2): Can be used |
|||||
| 1 | 0 | 0 | 1 | When only communication function is added: Relay contact output (alarm 1): Can be used Open collector output (alarm 2): Cannot be used |
|||||
| 0 | 1 | 0 | 1 | When both heating/cooling and communication functions are added: Relay contact output (alarm 1): Cannot be used Open collector output (alarm 2): Cannot be used |
|||||
Notes:
* When heating/cooling is selected, alarm output 1 cannot be used.
* When the communication function is selected, alarm output 2 cannot be used.
Example Part No.
(Ex) Part No. when the optional functions (of Heating/Cooling control: relay contact output + Communications function) is added on to the basic model are as follows;
Part No.: AKT21110101
Option
| Product name | Part No. |
|---|---|
| Shunt resistor (for Current input) | AKT4810 |
| Terminal cover | AKT2801 |
Note: When Current input is specified, a shunt resistor (sold separately) is required.
KT4 Series Controllers
| Base model | Power supply | Sensor input | Control output | Alarm output | Heating/ cooling control | Heater burnout alarm | Comm. function | Description |
|---|---|---|---|---|---|---|---|---|
| AKT4 | 48×48×95mm | |||||||
| 1 | 100 to 240V AC | |||||||
| 2 | 24V AC/DC | |||||||
| 1 | Multi-input (Thermocouple, RTD, DC Voltage and DC Current) | |||||||
| 1 | Relay contact output 1a 3A 250V AC | |||||||
| 2 | Non-contact voltage output (for SSR drive) | |||||||
| 3 | Current output | |||||||
| 1 | Relay contact output 1a (Alarm output 1) | |||||||
| 2 | Relay contact output 1a (Alarm output 2) | |||||||
| 0 | Not available | |||||||
| 4 | SSR output 0.3A 250V AC (Heating/Cooling control not supported when 2 alarm output points are selected) | |||||||
| 0 | Not available | |||||||
| 1 | 5A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| 2 | 10A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| 3 | 20A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| 4 | 50A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| Not available | ||||||||
| 1 | Available |
Notes:
* CT1 or CT2 for current detection is provided as an accessory when heater burn-out alarm function is added.
* Event output will be shared if you choose alarm output 2 and the heater burnout alarm.
Example Part No.
(Ex) Part No. when the optional functions (of Heating/Cooling control: SSR output + Communications function) is added on to the basic model are as follows;
Part No.: AKT41111401
Options
| Product name | Part No. |
|---|---|
| Shunt resistor (for Current input) | AKT4810 |
| Terminal cover | AKT4801 |
Note: When Current input is specified, a shunt resistor (sold separately) is required.
KT8 Series Controllers
| Base model | Power supply | Sensor input | Control output | Alarm output | Heating/ cooling control | Heater burnout alarm | Comm. function | Description |
|---|---|---|---|---|---|---|---|---|
| AKT8 | 48×96×98.5mm | |||||||
| 1 | 100 to 240V AC | |||||||
| 2 | 24V AC/DC | |||||||
| 1 | Multi-input (Thermocouple, RTD, DC Voltage and DC Current) | |||||||
| 1 | Relay contact output 1a1b 3A 250V AC | |||||||
| 2 | Non-contact voltage output (for SSR drive) | |||||||
| 3 | Current output | |||||||
| 1 | Relay contact output 1a (Alarm output 1) | |||||||
| 2 | Relay contact output 1a (Alarm output 2) | |||||||
| 0 | Not available | |||||||
| 1 | Relay contact output 1a | |||||||
| 2 | Non-contact voltage output (for SSR drive) | |||||||
| 3 | Current output | |||||||
| 0 | Not available | |||||||
| 1 | 5A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| 2 | 10A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| 3 | 20A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| 4 | 50A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| Not available | ||||||||
| 1 | Available |
Notes:
* CT1 or CT2 for current detection is provided as an accessory when heater burn-out alarm function is added.
* If a communication function is added, second main setup is not possible.
Example Part No.
(Ex)Part No. when the optional functions (of Alarm output; Alarm output 2 + Heating/Cooling control: Current output) are added on to the basic model are as follows;
Part No.: AKT8111230
Options
| Product name | Part No. |
|---|---|
| Shunt resistor (for Current input) | AKT4810 |
| Terminal cover | AKT8801 |
Note: When Current input is specified, a shunt resistor (sold separately) is required.
KT9 Series Controllers
| Base model | Power supply | Sensor input | Control output | Alarm output | Heating/ cooling control | Heater burnout alarm | Comm. function | Description |
|---|---|---|---|---|---|---|---|---|
| AKT9 | 96×96×98.5mm | |||||||
| 1 | 100 to 240V AC | |||||||
| 2 | 24V AC/DC | |||||||
| 1 | Multi-input (Thermocouple, RTD, DC Voltage and DC Current) | |||||||
| 1 | Relay contact output 1a1b 3A 250V AC | |||||||
| 2 | Non-contact voltage output (for SSR drive) | |||||||
| 3 | Current output | |||||||
| 1 | Relay contact output 1a (Alarm output 1) | |||||||
| 2 | Relay contact output 1a (Alarm output 2) | |||||||
| 0 | Not available | |||||||
| 1 | Relay contact output 1a | |||||||
| 2 | Non-contact voltage output (for SSR drive) | |||||||
| 3 | Current output | |||||||
| 0 | Not available | |||||||
| 1 | 5A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| 2 | 10A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| 3 | 20A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| 4 | 50A (Heater burn-out alarm not supported when control output is current output type/not supported when heating and cooling control is selected) | |||||||
| Not available | ||||||||
| 1 | Available |
Notes:
* CT1 or CT2 for current detection is provided as an accessory when heater burn-out alarm function is added.
* If a communication function is added, second main setup is not possible.
Example Part No.
(Ex) Part No. when the optional functions (of Alarm output; Alarm output 2 + Heating/Cooling control: Non-contact voltage output) are added on to the basic model are as follows;
Part No.: AKT9111220
Options
| Product name | Part No. |
|---|---|
| Shunt resistor (for Current input) | AKT4810 |
| Terminal cover | AKT9801 |
Note: When Current input is specified, a shunt resistor (sold separately) is required.
KT7 Series Controllers
| Base model | Power supply | Sensor input | Control output | Alarm output | Heating/ cooling control | Heater burnout alarm | Comm. function | Description |
|---|---|---|---|---|---|---|---|---|
| AKT7 | 22.5×75×100mm | |||||||
| 1 | 100 to 240V AC | |||||||
| 2 | 24V AC/DC | |||||||
| 1 | Multi-input (Thermocouple, RTD, DC Voltage and DC Current) | |||||||
| 1 | Relay contact output 1a 3A 250V AC | |||||||
| 2 | Non-contact voltage output (for SSR drive) | |||||||
| 3 | Current output | |||||||
| 1 | Open collector output (Alarm output 1) | |||||||
| 0 | Not available (without Heating/Cooling function) | |||||||
| 0 | Not available | |||||||
| 1 | 5A (not available for the Current output type) Open collector output | |||||||
| 2 | 10A (not available for the Current output type) Open collector output | |||||||
| 3 | 20A (not available for the Current output type) Open collector output | |||||||
| 4 | 50A (not available for the Current output type) Open collector output | |||||||
| Not available | ||||||||
| 8 | Available |
Notes:
* CT1 or CT2 for current detection is provided as an accessory when heater burn-out alarm function is added.
Example Part No.
(Ex) Part No. when the optional function (of Heater burnout alarm: 10A) is added on to the base model are as follows;
Part No.: AKT7111102
Options
| Product name | Part No. |
|---|---|
| Shunt resistor (for Current input) | AKT4811 |
Note: When Current input is specified, a shunt resistor (sold separately) is required.