FPX PLC Programmable Controls Specifications

PLC Programmable Controls FPX

Specifications for this product appear below.

Item Description
Relay output type Transistor output type
Power supply and I/O Specifications Power supply 100 to 240 V AC (AC power), 24 V DC (DC power)
Input 24V DC °C common
Output 2 A 0.5 A
Service power supply
(AC power type only)
0.15 A (C14)/ 0.4 A (C30/ C60)
Performance Specifications Number of I/O points C14 Input: 8 points, Output: 6 points
C30 Input: 16 points, Output: 14 points
C60 Input: 32 points, Output: 28 points
I/O points when expanded C14 Max. 328 points (When using FP0 expansion units and add-on cassette)
C30 Max. 352 points (When using FP0 expansion units and add-on cassette)
C60 Max. 382 points (When using FP0 expansion units and add-on cassette)
Operation speed 0.32μs/step
Program memory Flash ROM built-in (no battery backup required)
Program capcity 16 ksteps (C14), 32 ksteps (C30, C60)
Basic instructions 111
Applied instructions 216
Operation memory Internal relay ® 4096 points
Timer/counter (T/C) 1024 points
Data register (DT) 12285 words (C14), 32765 (C30, C60)
Special functions Pulse catch input 14 points 14 points
Interrupt input 14 points 14 points
Analog I/O Input: Max. 24 ch, Output: Max. 12 ch (When using FP0 analog unit)
Input: Max. 4 ch (When using add-on cassette)
Volume input 2 points (C14/C30), 4 points (C60)
High-speed counter Input of main unit Single-phase: 8 ch x Max. 10 kHz
2-phase: 4 ch Max. 5 kHz
Single-phase: 8 ch (High-speed: 4 ch, midium-speed: 4 ch)
2-phase: 4 ch (High-speed: 2 ch, midium-speed: 2ch)

With high-speed single-phase:
1 ch x Max. 100 kHz
2 ch x Max. 80 kHz
3 ch x Max. 60 kHz
4 ch x Max. 50 kHz
With high-speed 2-phase:
1 ch x Max. 35 kHz
2 ch x Max. 25 kHz
With medium-speed single-phase:
4 ch x Max. 10 kHz each
With Medium-speed 2-phase:
2 ch x Max. 5 kHz each
when pulse I/Ocassette installed Single-phase: 2 ch x Max. 80 kHz, 4 ch x Max. 50 kHz
2-phase: 1 ch x Max. 30 kHz, 2 ch x Max. 25 kHz
Pulse I/O cassette cannot be installed.
Pulse output Input of main unit - With high-speed 2 ch x Max. 100 kHz
For linear interpolation, compositespeed: 100 kHz
With medium-speed 2 ch x Max. 20 kHz
For linear interpolation, compositespeed: 20 kHz
when pulse I/Ocassette installed 1 ch x Max. 100 kHz, 2ch x Max. 80 kHz Pulse I/O cassette cannot be installed.
Serial interface RS232C.RS485, USB, Ethernet
Network function PLC Link, Computer link, Modem, Modbus-RTU
Other functions Program editing during RUN, Constant scan, 8-digit password, Program
Panasonic Electric Works Corporation of America Contact Print