| Item | Description | ||
|---|---|---|---|
| Power supply and I/O Specifications | Power supply | 24V DC | |
| Input | 24V DC ± common | ||
| Output | Transistor output type (NPN):Max. load current 0.2 A/ 5 to 24 V DC | ||
| Transistor output type (PNP):Max. load current 0.2 A/ 24 V DC | |||
| Relay output type:2 A 250 V AC, 2 A 30 V DC (4.5 A/common) | |||
| Performance Specifications | Number of I/O points | C10 | 10 points |
| C14 | 14 points | ||
| C16 | 16 points | ||
| C32/T32/F32 | 32 points | ||
| I/O points when expanded | C10 | Max. 106 points | |
| C14 | Max. 110 points | ||
| C16 | Max. 112 points | ||
| C32/T32/F32 | Max. 128 points | ||
| Operation speed | Up to 3000 steps | Basic instructions: 0.08 µsec min. Timer instructions: 2.2 µsec min. High-level instructions: 0.32 µsec (MV instruction) min. | |
| 3001st and later steps | Basic instructions: 0.58 µsec min. Timer instructions: 3.66 µsec min. High-level instructions: 1.62 µsec (MV instruction) min. | ||
| Program memory | EEP-ROM (no back up battery required) | ||
| Program capacity | 16 k steps(C10/C14/C16) / 32 k steps(C32/T32/F32) | ||
| Number of instructions | Basic | Approx. 110 | |
| High-level | Approx. 210 | ||
| Operation memory | Internal relay | 4096 points | |
| Timer/Counter | 1024 points | ||
| Data register (DT) | 12315 words(C10/C14/C16) /32765 words (C32/T32/F32) | ||
| Special functions | Pulse catch input | Total 8 points (with high speed counter) | |
| Interrupt input | |||
| Analog I/O | Input: Max. 24 ch, Output: Max. 12 ch (When using FP0 analog unit) | ||
| Volume input | — | ||
| High-speed counter | Single-phase: 6 points (50 kHz max. each) 2-phase: 3 channels (15 kHz max. each)* | ||
| Pulse output |
4 points (50 kHz max. each) Two channels can be controlled individually.* | ||
| Serial interface | RS232C.RS485 (when using C-NET adopter) | ||
| Network function | CC-Link, S-Link, Computer Link, Modem | ||
| Other functions | Rewriting in RUN mode, download in RUN mode (incl. comments) 8-character password setting, and program upload protection | ||
For the limitations while operating units, see the manual.